Mechanical equipment of buildings; a reference book for engineers and architects (1916)

Harding, Louis Allen, Willard, Arthur C. (Arthur Cutts), 1878-1960 · New York Wiley · leaf 459

An illustration from Mechanical equipment of buildings; a reference book for engineers and architects, 1916, leaf 459
line corresponding to 15 per cent relative humidity.Read horizontally to the left to the intersection with the 70 per cent cur\e. Thecorresponding dry-bulb temperature is 81° F., which is the required temperatureof the leaving air. The weight of moisture evapo-rated per lb. of dry air circulated… … 102° 108° 114° 120° AIR CONDITIONING, AIR WASHING, COOLING, AND DRYING 435 that a negative correction for radiation of approximately 1.6 per cent of the wet bulb depressionshould be made to obtain the true depression. A more refined type of apparatus, known as the Assmann Aspirating Psychrometer,…

Building · Heating · Ventilation