Mechanical equipment of buildings; a reference book for engineers and architects (1916)
Harding, Louis Allen, Willard, Arthur C. (Arthur Cutts), 1878-1960 · New York Wiley · leaf 472
uid or L.Then 0.2411 {t — /) = B.t.u. given up by one pound of air, r W = heat required to evaporate the weight of moisture added to the air./ W = 0.2411 (t — t) which is the equation for the adiabatic saturation of drj air.If the experiment were performed with dry air having an initial temperature… … Air Drier Fig. 1. Adiabatic SATUR-iTiox of Dry Air. the heat required for evaporation is 1065.6 X 0.00656 or 6.99 B.t.u. which is seen to be exactlythe same as the heat given up by the i)ound of dry air or 0.2411 X (75 — 46) or 6.99 B.t.u. Adiabatic Saturation of a Mixture of Air and Vapor. Assume…
Building · Heating · Ventilation
Internet Archive · University of Toronto, Robarts Library · Public Domain Mark 1.0. Free to use for anything.