Mechanical equipment of buildings; a reference book for engineers and architects (1916)
Harding, Louis Allen, Willard, Arthur C. (Arthur Cutts), 1878-1960 · New York Wiley · leaf 179
fiiel, and allow the auto-matic damper regulator to control the fire. WTien a low fire is all that is required allow theashes to accumulate on the grates to a depth of one to three or four inches, and when necessaryto clean the fire of clinkers, do so with the poker and hook, but do not shake the… … Fig. 47. grates. Do not allow the ashes to accumulate in the ash pit, and if any hot coals are shakentlwough the grates into the ash pit it is well to remove them at once. There should be at alltimes at least six inches of clear space below the grates. This precaution wiU prevent burning andwarping…
Building · Heating · Ventilation