International Library of Technology · Scranton, International Textbook Co. · leaf 649
5 5S. Conduits less than | inch inside diameter are notallowable and an outlet box should be provided at everyoutlet. When branch lines are taken off, a junction boxmust be provided. There should not be more than theequivalent of four right-angled bends between junctionboxes or there will be…