es in the condenserhead. On account of the vacuum maintained in the condenser the actual head, including frictionagainst which the circulating water pump operates, is approximately 15 to 20 feet above thelevel of water in the hot well. The amount of power required to do this is the entire amountof… … Fig. 21. Tomilson Barometric Condenser. 404 POWER PLANTS AND REFRIGERATION A vacuum of 28 referred to a 30 barometer is guaranteed by the manufacturers whensufficient cooling water at 70° F. is available to condense the amount of steam to be handled.A hot well temperature within 10 per cent of that…